Cixi Sheng An Electronics Co., Ltd.
Products
Contact Us
  • Contact Person : Mr. Lu Jinchun
  • Company Name : Cixi Sheng An Electronics Co., Ltd.
  • Tel : 86-574-63500211,13566582323
  • Fax : 86-574-63019806
  • Address : Zhejiang,Cixi,47 Chang Chi Sub-Road
  • Country/Region : China
  • Zip : 315300

HVAC vacuum pressure switch SA-50ZY

HVAC vacuum pressure switch SA-50ZY
Product Detailed
1.Supply OEM service 2.kinds of ranges to choose 3.IP54 4.we are manufacturer

Air differential pressure switches

Introduction:Air differential pressure switches can sense the pressure difference , vacuum, over pressure, poor flow of the incorrosive gas.Conventional applications include :+ Monitoring Filters blocked Alarm Device+ Monitoring air blower running status.+ Monitoring air of ventilative pipelines + Controlling the largest gas flow of variable gas volume + Monitoring the gas of combustion furnace.

Datasheet:

Model

Range

Min.actuating pressure

Interval:

SA-20xx

20pa-200pa

(0.2-2mbar)

20pa

20pa

SA-30xx

30pa-300pa

(0.3-3mbar)

30pa

20pa

SA-50xx

50pa-500pa

(0.5-5mbar)

50pa

50pa

SA-100xx

100pa-1000pa

(1-10mbar)

100pa

100pa

SA-500xx

500pa-2000pa

(5-20mbar)

500pa

100pa

Mounting Plate :” C”shape ,“Z”shape

Cover:”T”shape , “Y”shape

Max.differential pressure: 8000PaDegree of protection: IP54Electrical rating value: <2A / 250VACWorking temperature:-15~+60°CStorage temperature: -40~85°CInstallation direction: vertical(standard installation style)Hose connection: pipeΦ6.2mmWeight: 100 grams without bracketRepeatability: <±0.025mbar

Installation:Location: select a location where vibrations are minimal .Ambient temperature should be within the range of -15 / +60°C.The production calibration of the SA10X is made at room temperature ; mounting locations close to room temperatures are preferred . In systems with high humidity where condensation is possible, thus the entrance should point downwards.

Pressure connection and wiring:Pressure connections are marked with P1⊕&P2Θ,incorrect connections are forbidden.

Mounting instruction:The switch is preferably mounted with the diaphragm in a vertical plane , unless the device is set or calibrated for horizontal mounting as on special customer models. On these models the mounting position is indicated on the side of the control .It may be fastened directly to the duct, heater or panel as long as the mounting surface has minimal or no vibration .Pressure connections are marked +(high pressure ) and - (low or static pressure) .For more information, please read the diagram on the side of the control.

Note:To drill a hole through the plastic tube or pipe before installation, and also mount part of L-bracket on the spot(Standard setting).

Accessory consists of:(Φ6.2mm1.8m) plastic tubes, 1 L-bracket, 3srews, 2 pressure-adapted tubes.

Caution:+ The Pressure Switch should be mounted vertically which can prevent affecting on precision from inner atmosphere film weight.+ To prevent electrical shock or damage to equipment , when the cover is removed ,ensure the power supply is switched off.+ Complete wiring and check the connections before applying power . Incorrect wiring may cause permanent damage to the unit.

Wiring (Screw terminal):If the actual pressure is below dial setting, 1-2closed, while if the actual pressure is over dial setting, 1-3 closed.

System check:After proper installation and adjustment of the control ,the system should be checked by running at least one full cycle of the equipment .If anything appears to operate incorrectly , the wiring and components should be rechecked.

Repair and replacement:Repair is not possible .In case of a defective or improperly functioning control ,please check with your nearest supplier . when contacting the supplier for a replacement ,you should state the type /model number of the control .this number can be found on the side of the control.

HVAC vacuum pressure switch SA-50ZY



Copyright Notice @ 2008-2022 ECBAY Limited and/or its subsidiaries and licensors. All rights reserved.